Analog Communication
The device is capable of the following types of analog outputs:
• | 4–20 mA, isolated, current sourcing |
• | 0–10 Vdc for gas sample point identification |
Scale Analog Output: 4–20 mA
Full scale is 1000 ppm.
Normal gas readings are at 4–20 mA. The reading is proportional to the detected gas concentration.
For the factory default of 100% full scale setting (0.016 mA = 1 ppm):
Output (mA) |
Gas Concentration (ppm) |
4 |
0 |
5 |
63 |
6 |
125 |
7 |
188 |
8 |
250 |
9 |
313 |
10 |
375 |
11 |
438 |
12 |
500 |
13 |
563 |
14 |
625 |
15 |
688 |
16 |
750 |
17 |
813 |
18 |
875 |
19 |
937 |
20 |
1000 |
Analog Output Settings
Warm-up |
Default = 3.5 mA User adjustable between 0 and 3.75 mA |
Calibration (nonconfigurable) |
3.0 mA |
Fault |
Default = 2.0 mA User adjustable between 0.5 and 3.75 mA |
Device over range (nonconfigurable) |
21 mA |
0–10 Vdc
The voltage output can be used to identify any active gas sample line.
Sample Line |
Vdc |
Vdc |
1 |
1 |
1.0 |
2 |
2 |
1.5 |
3 |
3 |
2.0 |
4 |
4 |
2.5 |
5 |
5 |
3.0 |
6 |
6 |
3.5 |
7 |
7 |
4.0 |
8 |
8 |
4.5 |
9 |
- |
5.0 |
10 |
- |
5.5 |
11 |
- |
6.0 |
12 |
- |
6.5 |
13 |
- |
7.0 |
14 |
- |
7.5 |
15 |
- |
8.0 |
16 |
- |
8.5 |
While the device is in calibration mode, the output is 10 Vdc.