Communications Output

There are three options available to support digital outputs.

For a list of the registers that are available for exchange with the Modbus controller, refer to Appendix D: Modbus Holding Registers.

For a list of the BACnet Objects that are available for exchange with the BACnet controller, refer to Appendix E: BACnet Objects.

1. On the "Digital" tab of the "Outputs" screen, select one of the following:

 

2. If "None" is selected, no digital communication is configured.

3. If "Modbus" is selected, do the following:
a. Select "Edit".

 

 

 

 

b.   Select the "Device Address" field, and use the alphanumeric keypad pop-up to enter a value. Select to accept the value.
c.   Select a baud rate for the connection.
d.   Select the RS485 Termination check box.
e.   Select "Done".

4. "If "BACnet" is selected, do the following:
a. Select "Edit".

 

 

 

 

 

 

b.   Select the "MAC Address" field, and use the alphanumeric keypad pop-up to enter a value. Select to accept the value.
c.   Select the "Instance Number" field, and use the alphanumeric keypad pop-up to enter a value. Select to accept the value.
d.   Select a baud rate for the connection.

Use the scroll bar to move through the list of available options.

5. Select the "Analog" tab.
6. To adjust the default values, select the applicable field, and use the alphanumeric keypad pop-up to enter a value. Select to accept the value.
7. Select "Next".

For a list of default settings, refer to Appendix C: Default Settings.

8. The "Initial Setup" screen shows that all initial setup steps are complete. Select "Finished" to confirm the configuration settings and move to the "Initial Calibration" screen.