Gas Reading Accuracy

Factory Calibrated gases are gases whose behaviors have been characterized and built in to the Chillgard 5000 Firmware.

Gases in the extended library have not been specifically characterized. For these gases, the Chillgard 5000 will extrapolate the selected gas' behavior based on calibration data and the behavior of R134a.

Gas

Gas Concentration

Gas Reading Accuracy

As factory calibrated:

R-134A, R-404A, R-410A, R-407C, R-123, R1233zd(E), R-514A

1–50 ppm

51–1000 ppm

±1 ppm

±10% of reading

As factory calibrated extended library:

R-11, R-12, R-1234ze, R-22, R-407F, R-401A, R-407A, R-407C, R-422A, R-422D, R-426A, R-427A, R-454B, R-466A, R-515B, R-1234yf, R513A, R-514A

1–50 ppm

51–1000 ppm

±3 ppm

±30% of reading

As calibrated after installation:

R-134A, R-404A, R-410A, R-407C, R-123, R1233zd(E), R-11, R-12, R-1234ze, R-22, R-407F, R-401A, R-407A, R-422A, R-422D, R-427A, R-507, R-1234yf, R-513A, R-514A

1–50 ppm

51–1000 ppm

±1 ppm

±10% of reading

New added gases:

R-125, R-143A, R-152A, R-21, R-23, R-32, R-218, R-227, R-236FA, R-424A, R-426-A, R-427A, R-438A, R-448A, R-449A, R-452B, R-455B, R-455B, R-507A, R-508B

Ammonia (NH3)

1-50 ppm

51-1000 ppm

±5 ppm

± 10% of reading