Gas Reading Accuracy
Factory Calibrated gases are gases whose behaviors have been characterized and built in to the Chillgard 5000 Firmware.
Gases in the extended library have not been specifically characterized. For these gases, the Chillgard 5000 will extrapolate the selected gas' behavior based on calibration data and the behavior of R134a.
Gas |
Gas Concentration |
Gas Reading Accuracy |
As factory calibrated: R-134A, R-404A, R-410A, R-407C, R-123, R1233zd(E), R-514A |
1–50 ppm 51–1000 ppm |
±1 ppm ±10% of reading |
As factory calibrated extended library: R-11, R-12, R-1234ze, R-22, R-407F, R-401A, R-407A, R-407C, R-422A, R-422D, R-426A, R-427A, R-454B, R-466A, R-515B, R-1234yf, R513A, R-514A |
1–50 ppm 51–1000 ppm |
±3 ppm ±30% of reading |
As calibrated after installation: R-134A, R-404A, R-410A, R-407C, R-123, R1233zd(E), R-11, R-12, R-1234ze, R-22, R-407F, R-401A, R-407A, R-422A, R-422D, R-427A, R-507, R-1234yf, R-513A, R-514A |
1–50 ppm 51–1000 ppm |
±1 ppm ±10% of reading |
New added gases: R-125, R-143A, R-152A, R-21, R-23, R-32, R-218, R-227, R-236FA, R-424A, R-426-A, R-427A, R-438A, R-448A, R-449A, R-452B, R-455B, R-455B, R-507A, R-508B |
||
Ammonia (NH3) |
1-50 ppm 51-1000 ppm |
±5 ppm ± 10% of reading |