Technical Specifications / Equipment Ratings
Usage |
Indoor use only |
|
Overvoltage |
Category II |
|
Pollution |
Degree 2 |
|
ac Power |
100–240 Vac, 50/60 Hz, 200 VA maximum Supply voltage not to fluctuate more than ±10% |
|
Operating Temperature |
32–122°F (0 to 50°C) |
|
Operating Altitude Limit |
9762 ft (2975 m) |
|
Operating Humidity |
0 to 95%, noncondensing |
|
Ingress Protection |
IP54 |
|
Size |
Height x Width x Depth = 15.6 in. x 13.6 in. x 7.6 in. (39.6 cm x 34.5 cm x 19.3 cm) |
|
Weight |
4 point unit = 14 lb (6.4 kg) 8 point unit = 15 lb (6.8 kg) 16 point = 17 lb (7.7 kg) |
|
Sensor Type |
Photoacoustic Infrared |
|
Sample Line Tubing |
¼ in. OD x 1/8 in. ID |
Polyurethane (ether based) or metal with tubing |
6 mm OD x 4 mm ID |
||
Sample Line Length |
Up to 400 ft (121 m) for optimum performance, will support up to 1200 ft (366 m) |
|
Gases Chillgard 5000 |
R-11, R-12, R-22, R-123, R-134A, R-401A, R-404A, R-407A, R-407C, R-407F, R-410A, R-422A, R-422D, R-427A, R-454B, R-466A, R-513A, R-514A, R-515B, R-1233zd(E), R-1234yf, R-1234ze, R-125, R-143A, R-152A, R-21, R-23, R-32, R-218, R-227, R-236FA, R-424A, R-426A, R-438A, R-448A, R-449A, R-452B, R-455B, R-507A, R-508B |
|
Gases Chillgard 5000 |
NH3 |
|
Measuring Range |
0–1000 ppm |
|
Sensitivity (minimum detection) |
1 ppm for all listed R-gases 10 ppm for NH3 |
|
Accuracy (linearity) |
0– 50 ppm ±1 ppm, 51–1000 ppm ±10% of reading |
|
Sensor Response Time |
90% of gas reading < 19 sec 90% of gas reading < 60 sec for NH3 |
|
Relays |
5 Form C, 8A 250 Vac resistive SPDT |
|
Audible Alarm |
95 ±5 dB(A) at 24 in. (61 cm) maximum |
|
Communication Outputs |
4–20 mA sourcing, 250 Ohm load; 0–10 V, 2 K Ohm minimum load; RS485 Modbus RTU; |
|
Approvals |
CAN/CSA C22.2 No. 61010-1-12 UL 61010-1, 3rd edition IEC/EN 61010-1:2010 CE LVD: 2014/30/EU EMC: 2014/35/EU RoHS: 2011/65/EU EN 14624:2012 R134A UKCA LVD: SI 2016 No. 1101 EMC: SI 2016 No. 1091 RoHS: SI 2016 No. 3032 |