TB1, Fault Relay Connection

The standard configuration for the SPDT Fault relay is normally energized and non-latching. This configuration cannot be changed.

The Fault relay is activated during the time-out function, a low-power or loss-of-power condition, and a COPM Fault. For the duration of these conditions, the Fault relay de-energizes and the signal for analog output decreases to 0 mA (2 mA for a COPM Fault).

TB1
Position

Fault Relay

Relay Contact
(De-Energized)

Relay Contact
(Energized)

9

C

C

C

8

1

Normally Closed

Normally Open

10

2

Normally Open

Normally Closed