TB1, Fault Relay Connection
The standard configuration for the SPDT Fault relay is normally energized and non-latching. This configuration cannot be changed.
The Fault relay is activated during the time-out function, a low-power or loss-of-power condition, and a COPM Fault. For the duration of these conditions, the Fault relay de-energizes and the signal for analog output decreases to 0 mA (2 mA for a COPM Fault).
TB1 |
Fault Relay |
Relay Contact |
Relay Contact |
9 |
C |
C |
C |
8 |
1 |
Normally Closed |
Normally Open |
10 |
2 |
Normally Open |
Normally Closed |