Analog Output
Terminal Block |
Connection Point |
Block Name |
Setting |
---|---|---|---|
P1 |
Term 7 |
0 - 20 mA |
Analog Output |
The 0 to 20 mA output is a current signal that corresponds to the following:
Analog Output |
HART (1.25 mA)* |
HART (3.5 mA) |
HART Disabled/OFF |
---|---|---|---|
Startup |
1.25 mA |
3.5 mA |
0 to 0.2 mA |
FAULT Signal |
1.25 mA |
3.5 mA |
0 to 0.2 mA |
Test Mode |
1.5 mA |
3.5 mA |
1.5 ± 0.2 mA |
COPM Fault Signal |
2.0 mA |
3.5 mA |
2.0 ± 0.2 mA |
Ready Signal |
4.05 ± 0.2 mA |
4.05 ± 0.2 mA |
4.05 ± 0.2 mA |
INSTANT ALARM Signal |
16.0 ± 0.2 mA |
16.0 ± 0.2 mA |
16.0 ± 0.2 mA |
SUSTAINED ALARM Signal |
20.0 ± 0.2 mA |
20.0 ± 0.2 mA |
20.0 ± 0.2 mA |
Bluetooth Load | 3.0 mA | 3.0 mA | 3.0 mA |
NOTE: Refer to the FL5000 Modbus or HART manual for Current Range selection.
|