Certifications

Approvals subject to change without notice and may differ based on configuration, part number and/or country. Contact Customer Service or check the approval label on the product for specific approval information.

Region Certification Agency Primary Standard Details
United States Performance
FM21US0085X
FM FM 3260 See Section 0.1 (High/Med/Low Sensitivity)
Hazardous Location (Division)
FM21US0085X
FM FM 3611, FM 3615,
FM 3616
Class I, Div. 1, Groups B, C, D
Class II/III, Div. 1/2, Groups E, F, G
Class I, Div. 2, Groups A, B, C, D
T4 (-40°C ≤ Ta ≤ +80°C)
Type 6P, IP66/67
Hazardous Location (Zone)
FM21US0085X
FM UL 60079-1,
UL 60079-31
Class I, Zone 1, AEx db IIC T4 Gb
Zone 21, AEx tb IIIC T135°C Db
-40°C ≤ Ta ≤ +80°C, IP66/67
Canada Performance
FM23CA0006X
FM ULC-ORD-C386 See Section 0.1 (High/Med/Low Sensitivity)
Electrical Safety CSA UL/CSA 61010-1,
CSA C22.2 #94.2
Pollution Degree 4, Type 6P
Hazardous Location (Division)
CSA CSA C22.2 #25, #30, #213 Class I, Div. 1, Groups B, C, D
Class II/III, Div. 1, Groups E, F, G
T4 (-40°C ≤ Ta ≤ +80°C), IP66/67
Class I, Div. 2, Groups A, B, C, D
T4 (-50°C ≤ Ta ≤ +80°C), IP66/67
Hazardous Location (Zone)
FM23CA0006X
FM CSA C22.2 #60079-1,
#60079-31
Ex db IIC T4 Gb, Ex tb IIIC T135C Db,
-40°C ≤ Ta ≤ +80°C, IP66/67
European Union & UK Performance (Construction Product Regulation)
1725-CPR-UKE1019
2809-CPR-E0030
FM EN 54-10 See Section 0.1 (Class 1 for High & Medium Sensitivity, Class 2 for Low Sensitivity)
Performance
(EMC Directive)
FM EN 50130-4 Compliant
Hazardous Location (ATEX Directive)
FM21ATEX0049X
FM21UKEX0215X
FM EN 60079-1,
EN 60079-31
II 2 G Ex db IIC T4 Gb,
II 2 D Ex tb IIIC T135C Db,
-55°C ≤ Ta ≤ +80°C, IP66/67
Brazil NCC YY.NNNN NCC ABNT NBR IEC 60079-0, ABNT NBR IEC 60079-1, ABNT NBR IEC 60079-31 II 2 G Ex db IIC T4 Gb,
II 2 D Ex tb IIIC T135C Db,
-55°C ≤ Ta ≤ +80°C, IP66/67
International Hazardous Location
IECEx FMG 21.0020X
FM IEC 60079-1,
IEC 60079-31
Ex db IIC T4 Gb, Ex tb IIIC T135C Db,
-55°C ≤ Ta ≤ +80°C, IP66/67
SIL Capability FM IEC 61508 Series SIL 2 & SIL 3 Capable

NOTE: For Special Conditions of Safe Use (X) see Safety Regulations.