Time Delay Settings

When set to a minimum of 8 seconds, Time delay set via dipswitch guarantees that FL5000 will not go into SUSTAINED ALARM mode (20 mA) if the flame source is removed within 50% of set delay time from the start of flame. The unit will go into INSTANT ALARM mode (16 mA) upon seeing a flame source.