System Verification
- Connect the detector(s) to the SENTRY io.
- Configure the SENTRY io.
- Verify detector information on the dashboard.
- Test the detector alarm setpoints with the application or simulation of gas.
- Test the buzzer response to alarm state. Verify the volume level of the buzzer is sufficient for the ambient noise level in the environment.
- Exercise the FAULT relay to ensure proper activation.
- Export the .csv file to review the cause and effect relationships.
- Verify the Cause and Effect logic actions to ensure all consequences execute as intended.