Technical Specifications

Mechanical Specifications
SENTRY io size 558.8 mm x 447.68 mm x 241.3 mm
SENTRY io weight 20 kg
Materials Fiberglass
Ratings NEMA-4X, IP65
Operating and storage temperature range -20 °C to 65 °C
Humidity 20-90% relative humidity (non-condensing)
Atmospheric pressure range 86 kPa – 108 kPa
Electrical Specifications
Input power types and ratings 100-240 VAC 50/60 HZ (autoswitching input)
Power consumption (controller alone) 1.4 amps at 24 VDC
Power capacity – max field device power available at 24 VDC 8.6 amps at 24 VDC
Maximum number of inputs

16 analog or 16 analog with HART gas detectors

6 discrete dry contact inputs

Input types supported

Analog with HART, Discrete dry contact

Maximum number of outputs

56 relays

16 analog outputs

Output types supported Relays, Analog outputs
Output relay contacts

Maximum load:

  • 2 A at 240 VAC resistive
  • 2 A at 30 VDC resistive

Minimum load:

  • 1 mA, 5 VDC
Ground fault monitoring? No
Maximum loop impedance 251 Ohms
Display/Functional Indicators
Touchscreen size and type 178 mm LCD
Functional Indicators System Normal, Alarm, and Fault (located on touchscreen)
Pre-programmed functions Remote Reset and Remote Silence dry contact inputs
Remote access capability

Remote display is an available option through Ethernet connection

Programming and Configuration
Programming logic functions supported AND, OR, 2 of N, and 3 of N logical equations
Program storage/retrieval/back up options USB or SD card
Digital communications supported MODBUS TCP/IP, MODBUS RTU (optional), Ethernet IP/DLR (consult factory)
Certifications

Certified for installation and use in Class I, Div. 2, Group A, B, C, D, Class I, Zone 2 Group IIC classified areas.

Certified by FM Approvals for US, Canada (FM22CA0007), ATEX (FM22ATEX0006), IECEx (IECEx FMG 22.0007), UKCA (FM23UKEX0046)

Performance certification includes: IEC/EN/UL/FM 60079-29-1, IEC/EN 60079-29-4, EN 50104, FM 6320, FM 6325, FM 6340, ANSI/FM 12.13.04, ANSI/ISA 92.00.01, and ANSI/ISA 92.04.01, UL/FM/EN/IEC 62990-1 as a safety monitor (SM)

EMC Directive, REACH Regulation and RoHS Directive compliant