Technical Specifications
Mechanical Specifications | |
SENTRY io size | 558.8 mm x 447.68 mm x 241.3 mm |
SENTRY io weight | 20 kg |
Materials | Fiberglass |
Ratings | NEMA-4X, IP65 |
Operating and storage temperature range | -20 °C to 65 °C |
Humidity | 20-90% relative humidity (non-condensing) |
Atmospheric pressure range | 86 kPa – 108 kPa |
Electrical Specifications | |
Input power types and ratings | 100-240 VAC 50/60 HZ (autoswitching input) |
Power consumption (controller alone) | 1.4 amps at 24 VDC |
Power capacity – max field device power available at 24 VDC | 8.6 amps at 24 VDC |
Maximum number of inputs |
16 analog or 16 analog with HART gas detectors 6 discrete dry contact inputs |
Input types supported |
Analog with HART, Discrete dry contact |
Maximum number of outputs |
56 relays 16 analog outputs |
Output types supported | Relays, Analog outputs |
Output relay contacts |
Maximum load:
Minimum load:
|
Ground fault monitoring? | No |
Maximum loop impedance | 251 Ohms |
Display/Functional Indicators | |
Touchscreen size and type | 178 mm LCD |
Functional Indicators | System Normal, Alarm, and Fault (located on touchscreen) |
Pre-programmed functions | Remote Reset and Remote Silence dry contact inputs |
Remote access capability |
Remote display is an available option through Ethernet connection |
Programming and Configuration | |
Programming logic functions supported | AND, OR, 2 of N, and 3 of N logical equations |
Program storage/retrieval/back up options | USB or SD card |
Digital communications supported | MODBUS TCP/IP, MODBUS RTU (optional), Ethernet IP/DLR (consult factory) |
Certifications | |
Certified for installation and use in Class I, Div. 2, Group A, B, C, D, Class I, Zone 2 Group IIC classified areas. Certified by FM Approvals for US, Canada (FM22CA0007), ATEX (FM22ATEX0006), IECEx (IECEx FMG 22.0007), UKCA (FM23UKEX0046) Performance certification includes: IEC/EN/UL/FM 60079-29-1, IEC/EN 60079-29-4, EN 50104, FM 6320, FM 6325, FM 6340, ANSI/FM 12.13.04, ANSI/ISA 92.00.01, and ANSI/ISA 92.04.01, UL/FM/EN/IEC 62990-1 as a safety monitor (SM) EMC Directive, REACH Regulation and RoHS Directive compliant |