Troubleshooting

  Condition Corrective Action
1 Unit does not have power
  • Check physical connection—Confirm internal cabling is not frayed or disconnected
  • Check power supply LED indicators
  • Check power supply load—Confirm the power load was properly calculated
2 Instrument was not auto-detected
  • Ensure instrument supports HART—If not HART supported, used generic configuration

    NOTE: The X5000/S5000 second sensor does not auto detect with HART and must be manually added as a generic sensor.

  • Ensure instrument is properly wired
3 Buzzer is not working or is not loud enough
  • Ensure damper is not closed
  • Ensure buzzer is properly wired
4 Channel does not appear to be showing proper reading
  • Ensure instrument is properly wired
  • Ensure there are no faults with instrument
  • Ensure input module is properly secured and connected to bus
  • Ensure detectors are set in default analog settings

    NOTE: For X5000 and S5000 sensors, the 0 value is 4.04 mA so the readout at the SENTRY io might be slightly higher than 0 – this is normal operation.

5 Failed to recognize hardware Ensure input module is properly secured and connected to bus
6 Touchscreen not responding
  • Ensure user is not wearing touch-resistent gloves
  • Clean hands and clean screen
7 Relay not operating as expected
  • Ensure relay module is properly secured and connected to bus
  • Ensure all preceding modules are properly secured and connected to bus
  • Ensure relay condition is properly configured in relay assignments and cause & effect programming
  • Ensure relay is properly wired for configuration
  • Ensure relay is wetted, if required by application
  • Ensure current is not below minimum requirement for relay
  • Ensure relay configuration meets system specifications (example: less than 2 amps)
  • Check for damaged equipment
8 Analog output is not working Ensure wiring is properly installed to support desired configuration
9 Local transmitter settings do not match controller settings (example: set-points, scale, units)
  • Ensure controller settings match expected values for connected instruments
  • On the Setpoints screen in the SmartStart configuration wizard, select Write A1 & A3 alarm set-points to MSA detectors via HART
10 Instrument reading does not match controller reading
  • Ensure instrument is properly wired
  • Ensure instrument is properly configured
  • Check instrument voltage
  • Ensure detectors are set in default analog settings
11 Channel not reporting an alarm
  • Ensure instrument is properly wired
  • Ensure alarm condition is properly configured in relay assignments and cause & effect programming
  • Ensure local and controller set-points are configured as expected
  • Ensure alarm condition is not inhibited
12 Discrete/Digital Input not working
  • Ensure input is not inhibited
  • Ensure input is properly wired
  • Ensure input is enabled
  • Check local vs. SENTRY io setpoints
13 System time incorrect
  • Check settings
  • Check NPT setting
14 Communication output not working
  • Check settings (IP address, etc)
  • Check wiring/cableing
15 Forgotten/lost password Call MSA
16 TagName is not correct Check setting for instrument on channel
17 Manual Identification

Refer to detector for necessary manual identification information

18 Wrong instrument connected to channel
  • Check wiring
  • Check proper instrument is connected to proper wire terminals
19 Sensor 2 not displayed for dual sensor transmitter (X5000 and S5000)

HART devices only report sensor 1. Use the generic setup to manually configure sensor 2.

20 Wrong user manual shown for channel
  • Check correct instrument is connected
  • Check correct manual is uploaded
21 Change from 3 to 2 setpoints (or vice versa) Check configuration and change, if needed
22 Discrete/digital input not latching

Check settings on controller

NOTE: Once 3 alarm setpoint configuration is selected, 2 setpoint configuration is not allowed due to inadvertent changes to Cause & Effect and Voting. Changing to 2 setpoint configuration requires Reset Configuration.

23 Remote silence not working Check wiring
24 Remote reset not working
  • Check wiring
  • Check active alarms
25 Relay contact not powered Most relays are dry—Check manual for wetting contact
26 View/export program logic
  • Check logic in cause & effect settings
  • Export logic in cause & effect settings
27 Cannot configure "two relay voting" scheme Create second voting scheme that uses same inputs with a different output
28 Not all channels displayed on dashboard
  • Change view configuration
  • Follow arrow to next screen showing additional channels
29 Fault code on screen Any fault code shown is derived from HART command 48. See instrument display for more information
30 Can I export trends Copy file from SD card directory <dir>
31 Can I export cause & effect Copy file from SD card directory <dir>
32 Oxygen Alarms can't write to detectors Note that Alarm set-points for Oxygen sensors cannot be written to the detectors. This is because some Oxygen sensors utilize upward acting alarms and SENTRY io uses only downward acting alarms for Oxygen therefore this rule prevents inconsistencies in operation. Setpoints at these detectors need to be altered manually.