Maintenance Intervals

The following maintenance activities are required.

Interval Function
 

During Commissioning

Perform bump check or calibration to confirm instrument functionality.
Check LEDs for proper operation.*
Check for proper buzzer and relay operation.*
Check signal transmission to the BMS/BAS (central controller) if connected.*
  Periodic Maintenance Interval** Inspection by trained service personnel.
Check LEDs for proper operation.*
Check for proper buzzer and relay operation.*
Check signal transmission to the BMS/BAS (central controller) if connected.*
Calibrate the sensor or contact MSA to purchase a factory‑calibrated sensor.
As Required Replace sensor module(s)

* Feature may be activated via Modbus commands or monitor X-Series App.

** Typical maintenance frequency may vary by sensor type.

Sensor Type Maintenance Interval

Typical Sensor Lifetime

(Individual sensor performance can vary based on specifics of sensor usage.)

Semiconductor*

6 months after commissioning

12 months thereafter

~5 years
Infrared 12 months 5+ years

* Sensors should be checked, calibrated, and potentially replaced after exposure to significant concentrations of gas, which can shorten the sensor lifetime and/or reduce its sensitivity.