X30 & X50 Gas Monitors Technical Specifications
NOTE: The tables below details specifications for X30 & X50 models. For information on sensors and detected gases, see Sensor Specifications
| Mode of Operation | Analog Output State | 1-5V | 2-10V | 4-20mA |
|---|---|---|---|---|
| Manual / Test Mode | Manual - 0 | 1-5V | 2-10V | 4-20mA |
| Instrument Fault | Fault - 1 | ≤ 0.3V | ≤ 0.6V | ≤ 1.2mA |
| Offline Mode / Maintenance | Offline - 2 | 0.75V | 1.5V | 3mA |
| Drift Below Zero | Underflow - 3 | 0.95V | 1.9V | 3.8mA |
| Measuring Range Exceeded (Over range) | Overflow - 4 | 5.12V | 10.25V | 20.5mA |
| Normal Operation | Normal - 5 | 1-5V | 2-10V | 4-20mA |
| Disable Sensor (X50 only) | Zero - 6 | 0V | 0V | 0mA |
| Category | Specifications | |||
|---|---|---|---|---|
| Output Signal Specifications | Modbus RTU over RS-485 | Baud rate: | 9,600 or 19,200 (selectable) | |
| Start bits: | 1 | |||
| Data bits: | 8 | |||
| Parity: | None, odd, even (selectable) | |||
| Stop bits: | 1 or 2 (selectable) | |||
| Retry time: | 500 ms, min time between retries | |||
| End of message: | Silent 3.5 characters | |||
| Power Supply and Relays | Operating Voltage |
24 VDC +/- 20% 24 VAC +/- 20%, 50/60 Hz |
||
| Inrush Current | 1.5 A | |||
| Operating current, max. |
X30 - 8 W, (333 mA @ 24 VDC) X50 - 14 W, (583 mA @ 24 VDC) |
|||
| Relay rating |
X30: DPDT, 24 V AC/DC, 2A X50: DPDT, 24 V AC/DC, 2A |
|||
| Audible alarm | Internal Buzzer >90 dB at 4” (10 cm) | |||
| Alarm delay | 0 to 15 minutes (selectable) | |||
| Wiring | Power and analog signal | 2-Wire shielded cable, 16 to 20 AWG (0.5 to 1.5 mm2) | ||
| Modbus network | 3-Wire, twisted pair + ground, shielded cable with 120 Ω characteristic impedance, 16 to 24 AWG (0.5 to 1.5 mm2) | |||
| Cable Fittings |
M16 or M20 metric size cable glands 1/2" and 3/4" NPT plastic and metal conduit Not intended for use with threaded metal conduit / hubs |
|||
| Temperature | Installation requires the use of field wiring cable with temperature limit >60C | |||
| Physical Specifications | Enclosure and sensor housing |
Enclosure Housing: Polycarbonate Sensor Housing: ABS |
||
| Enclosure Ingress Protection |
IP66 Type 4 |
|||
| Weight (Approx.) |
X30: 13.7 oz (388 g) X50: 16.6 oz (471 g) |
|||
| Enclosure Size (WxHxD) (Approx.) |
X30: 164 x 132 x 76 mm X50: 164 x 160 x 84 mm |
|||
| Environmental | Operating temperature | - 40° to 122 ºF (-40 to 50 ºC) | ||
| Storage temperature | - 4° to 104 ºF (-20 to 40 ºC) | |||
| Humidity |
5 to 90 %RH, non-condensing |
|||
| Pressure | 23.6 to 32.5 inch Hg / 800 to 1,100 mbar | |||
| Elevation | 0 to 10,000 ft. (3050 m) altitude | |||
| Sensors | See Sensor Specifications | |||
| Influences | For influences on the measurement performance and restrictions of a particular sensor see sensor data sheet. | |||
| Product Approvals | UL / CSA / EN 61010-1, CE (EMC Directives) | |||
| Product Design Standards | EN 14624 (Indicating Device), EN 50270. Testing performed to FM TD 221. | |||
| Industry Codes & Regulations | Supports ASHRAE 15, CSA B52.2, EN 378, F-Gas Regulation, IIAR CO2 | |||
X10 Remote Gas Sensor Technical Specification
NOTE: The X10 Remote Gas Sensor is not a standalone device. Power and communications specifications intended to reflect connection to X50 base transmitter.
| Category | Specifications | ||
|---|---|---|---|
|
Output Signal Specifications (Connected to X50 device and unable to be modified by user) |
Modbus RTU over RS-485 | ||
| Baud rate: | 9,600 | ||
| Start bits: | 1 | ||
| Data bits: | 8 | ||
| Parity: | None | ||
| Stop bits: | 1 | ||
| Retry time: | 500 ms, min time between retries | ||
| End of message: | Silent 3.5 characters | ||
| Power Supply | Operating Voltage | 12VDC (to be supplied from X50 transmitter only) | |
| Wiring | Power and Communication | 4-Wire shielded cable, 18AWG (0.75mm^2) | |
| Cable Fittings |
M16 metric size cable glands or 1/2" NPT plastic and metal conduit. Not intended for use with threaded metal conduit/hubs. |
||
| Temperature | Installation requires the use of field wiring cable with temperature limit >60C | ||
| Physical Specifications | Enclosure and sensor housing |
Enclosure Housing: Polycarbonate Sensor Housing: ABS |
|
| Enclosure Ingress Protection |
IP66 TYPE 4 |
||
| Weight (Approx.) |
6.4 oz (181 g)
|
||
| Enclosure Size (WxHxD) (Approx.) |
106 x 82 x 55 mm |
||
| Environmental | Operating temperature | - 40° to 122 ºF (-40° to 50 ºC) | |
| Storage temperature | - 4° to 104 ºF (-20° to 40 ºC) | ||
| Humidity |
5 to 90 %RH, non-condensing |
||
| Pressure | 23.6 to 32.5 inch Hg / 800 to 1,100 mbar | ||
| Elevation | 0 to 10,000 ft. (3050 m) altitude | ||
| Sensors | See Sensor Specifications | ||
| Influences | For influences on the measurement performance and restrictions of a particular sensor see sensor data sheet. | ||
| Product Approvals | UL / CSA / EN 61010-1, CE (EMC Directives) | ||
| Product Design Standards | EN 14624 (Indicating Device), EN 50270. Testing performed to FM TD 221 | ||
| Industry Codes & Regulations | Supports ASHRAE 15, CSA B52.2, EN 378, F-Gas Regulation, IIAR CO2 | ||