X30 & X50 Gas Monitors Technical Specifications

NOTE: The tables below details specifications for X30 & X50 models. For information on sensors and detected gases, see Sensor Specifications

Mode of Operation Analog Output State 1-5V 2-10V 4-20mA
Manual / Test Mode Manual - 0 1-5V 2-10V 4-20mA
Instrument Fault Fault - 1 ≤ 0.3V ≤ 0.6V ≤ 1.2mA
Offline Mode / Maintenance Offline - 2 0.75V 1.5V 3mA
Drift Below Zero Underflow - 3 0.95V 1.9V 3.8mA
Measuring Range Exceeded (Over range) Overflow - 4 5.12V 10.25V 20.5mA
Normal Operation Normal - 5 1-5V 2-10V 4-20mA
Disable Sensor (X50 only) Zero - 6 0V 0V 0mA
Category Specifications
Output Signal Specifications Modbus RTU over RS-485 Baud rate:   9,600 or 19,200 (selectable)
Start bits:   1
Data bits:   8
Parity:   None, odd, even (selectable)
Stop bits:   1 or 2 (selectable)
Retry time:   500 ms, min time between retries
End of message:   Silent 3.5 characters
Power Supply and Relays Operating Voltage

24 VDC +/- 20%

24 VAC +/- 20%, 50/60 Hz

Inrush Current 1.5 A
Operating current, max.

X30 - 8 W, (333 mA @ 24 VDC)

X50 - 14 W, (583 mA @ 24 VDC)

Relay rating

X30: DPDT, 24 V AC/DC, 2A

X50: DPDT, 24 V AC/DC, 2A

Audible alarm Internal Buzzer >90 dB at 4” (10 cm)
Alarm delay 0 to 15 minutes (selectable)
Wiring Power and analog signal 2-Wire shielded cable, 16 to 20 AWG (0.5 to 1.5 mm2)
Modbus network 3-Wire, twisted pair + ground, shielded cable with 120 Ω characteristic impedance, 16 to 24 AWG (0.5 to 1.5 mm2)
Cable Fittings

M16 or M20 metric size cable glands 1/2" and 3/4" NPT plastic and metal conduit

Not intended for use with threaded metal conduit / hubs

Temperature Installation requires the use of field wiring cable with temperature limit >60C
Physical Specifications Enclosure and sensor housing

Enclosure Housing: Polycarbonate

Sensor Housing: ABS

Enclosure Ingress Protection

IP66

Type 4

Ingress Protection Ratings

Weight (Approx.)

X30: 13.7 oz (388 g)

X50: 16.6 oz (471 g)

Enclosure Size (WxHxD) (Approx.)

X30: 164 x 132 x 76 mm

X50: 164 x 160 x 84 mm

Environmental Operating temperature - 40° to 122 ºF (-40 to 50 ºC)
Storage temperature - 4° to 104 ºF (-20 to 40 ºC)
Humidity

5 to 90 %RH, non-condensing

Pressure 23.6 to 32.5 inch Hg / 800 to 1,100 mbar
Elevation 0 to 10,000 ft. (3050 m) altitude
Sensors See Sensor Specifications
Influences For influences on the measurement performance and restrictions of a particular sensor see sensor data sheet.
Product Approvals UL / CSA / EN 61010-1, CE (EMC Directives)
Product Design Standards EN 14624 (Indicating Device), EN 50270. Testing performed to FM TD 221.
Industry Codes & Regulations Supports ASHRAE 15, CSA B52.2, EN 378, F-Gas Regulation, IIAR CO2

X10 Remote Gas Sensor Technical Specification

NOTE: The X10 Remote Gas Sensor is not a standalone device. Power and communications specifications intended to reflect connection to X50 base transmitter.

Category Specifications

Output Signal Specifications (Connected to X50 device and unable to be modified by user)

  Modbus RTU over RS-485    
Baud rate: 9,600
Start bits: 1
Data bits: 8
Parity: None
Stop bits: 1
Retry time: 500 ms, min time between retries
End of message: Silent 3.5 characters
Power Supply Operating Voltage 12VDC (to be supplied from X50 transmitter only)
Wiring Power and Communication 4-Wire shielded cable, 18AWG (0.75mm^2)
Cable Fittings

M16 metric size cable glands or 1/2" NPT plastic and metal conduit.

Not intended for use with threaded metal conduit/hubs.

Temperature Installation requires the use of field wiring cable with temperature limit >60C
Physical Specifications Enclosure and sensor housing

Enclosure Housing: Polycarbonate

Sensor Housing: ABS

Enclosure Ingress Protection

IP66

TYPE 4

Ingress Protection Ratings

Weight (Approx.)

6.4 oz (181 g)

 

Enclosure Size (WxHxD) (Approx.)

106 x 82 x 55 mm

Environmental Operating temperature - 40° to 122 ºF (-40° to 50 ºC)
Storage temperature - 4° to 104 ºF (-20° to 40 ºC)
Humidity

5 to 90 %RH, non-condensing

Pressure 23.6 to 32.5 inch Hg / 800 to 1,100 mbar
Elevation 0 to 10,000 ft. (3050 m) altitude
Sensors See Sensor Specifications
Influences For influences on the measurement performance and restrictions of a particular sensor see sensor data sheet.
Product Approvals UL / CSA / EN 61010-1, CE (EMC Directives)
Product Design Standards EN 14624 (Indicating Device), EN 50270. Testing performed to FM TD 221
Industry Codes & Regulations Supports ASHRAE 15, CSA B52.2, EN 378, F-Gas Regulation, IIAR CO2