Detector Field of View

Each FL5000 Flame Detector has a maximum range of 310 feet (95 m).

The FOV has its vertex at the center of the detector. Horizontal FOV is measured in the horizontal plane going through the center axis of the detector, and vertical FOV is measured in the vertical plane going through the same axis. Both horizontal and vertical FOV are defined for high, medium and low sensitivity settings of the FL5000, as shown in the charts below.

n-Heptane (1' x 1')

Horizontal High Med Low
310' 140’ 70'
+15° 310' 140’ 70'
-15° 310' 140’ 70'
+ 30° 265’ 140’ 70'
- 30° 265’ 140’ 70'
+ 45° 110' 40' 35'
- 45° 110' 50' 35'
Vertical High Med Low
310' 140’ 70'
+15° 310' 140’ 70'
-15° 310' 140’ 70'
+ 30° 265’ 140’ 70'
- 30° 265’ 140’ 70'
- 45° 110' 40' 35'

Figure 10 n-Heptane Field of View

The following fuels have been tested and their applicable field of view charts and sensitivity details can be viewed in Certifications.

Heptane JP4 (2' x 2')
Gasoline JP5 (1' x 1')
Methanol JP5 (2' x 2')
Methane JP8 (1' x 1')
Butane JP8 (2' x 2')
Propane Jet A (1' x 1')
Ethane Jet A (2' x 2')
Ethanol Marina Fuel
Crude Oil Kerosene
Ethylene Glycol Xylene
Isopropanol MEK
Diesel Wood (6" x 6")
JP4 (1' x 1') Cardboard (6" x 6")