Switch Selectable Options

All settings on the FL5000 are selected via a dipswitch on the Power/Relay board or via Modbus (overrides switch settings).

To set these options:

1. Remove the detector head from the Base Assembly and locate the dipswitch per the Dipswitch Location figure in Time Delay Settings
2. On the dipswitch, ON/CLOSED means the switch is pushed in on the side labeled ON or CLOSED (opposite the OPEN side).
3. OFF/OPEN means the switch is pushed in on the side with the number corresponding to the switch position or the side labeled OPEN – refer to Time Delay Settings for dipswitch assignments.

The settings for the INSTANT ALARM and SUSTAINED ALARM outputs are covered in Terminal Connections.

Figure 19 Dipswitch Location

 

Position

1 2 3 4 5 6 7 8 9 10 11 12
High Sensitivity OFF OFF - - - - - - - - - -
Medium Sensitivity ON OFF - - - - - - - - - -
Low Sensitivity OFF ON - - - - - - - - - -
0 Sec Alarm Time Delay - - ON ON - - - - - - - -
8 Sec Alarm Time Delay - - OFF ON - - - - - - - -
10 Sec Alarm Time Delay - - OFF OFF - - - - - - - -
14 Sec Alarm Time Delay - - ON OFF - - - - - - - -
Sustained Alarm Non-Latching - - - - OFF - - - - - - -
Sustained Alarm Latching - - - - ON - - - - - - -
Instant Alarm Non-Latching - - - - - OFF - - - - - -
Instant Alarm Latching - - - - - ON - - - - - -
Sustained Alarm Normal De-Energized - - - - - - OFF - - - - -
Sustained Alarm Normal Energized - - - - - - ON - - - - -
Instant Alarm Normal De-Energized - - - - - - - OFF - - - -
Instant Alarm Normal Energized - - - - - - - ON - - - -
LEDs - Standard Mode - - - - - - - - OFF - - -
LEDs - Alternate PEMEX Mode - - - - - - - - ON - - -
HART Enabled - - - - - - - - - OFF - -
HART Disabled - - - - - - - - - ON - -
Window Heater Disabled - - - - - - - - - - OFF -
Window Heater Enabled - - - - - - - - - - ON -
Test Lamp AO Mode Disabled - - - - - - - - - - - OFF
Test Lamp AO Mode Enabled - - - - - - - - - - - ON
BLE Enabled ON
BLE Disabled OFF
AO Sink Sink
AO Source Source