Sustained Alarm Relay

Terminal Block

Connection Point

Block Name

User Relay Settings

Normally De-energized

Normally Energized

P2

Term 5

ALM_SUS 2

Sustained Alarm NO

Sustained Alarm NC

P2

Term 6

ALM_SUS 1

Sustained Alarm NC

Sustained Alarm NO

P2

Term 7

ALM_SUS CM

Sustained Alarm Common

Sustained Alarm Common

NOTE: NO = Normally Open; NC = Normally Closed

The connections are to the single pole, double throw (SPDT) SUSTAINED ALARM relay. SUSTAINED ALARM output is time delayed for 0, 8, 10, or 14 seconds. This time delay can be set by Modbus (RS-485) or the user selectable dipswitch per Switch Selectable Options.

Note that a minimum time delay of 8 seconds can be applied if the flame source is removed within 50% of set delay time from the start of flame. Please refer to Time Delay Settings. If set via Modbus below 8 seconds, the detector may go into alarm even if the flame source is removed within 50% of the delay time.

The SUSTAINED ALARM output can be normally energized or de-energized, latching or non-latching, and these options are also set via Modbus or by a dipswitch. The SUSTAINED ALARM relay contact rating is 8 A @ 24 VDC. Refer to the figure in Sustained Alarm Relay for all relay connections.