Specifications

System Specifications

Typical Response Time: 10 seconds, see Certifications for FM Approval response times
Field of View*: ±30° @ 210 ft (64 m), ±45° @ 110 ft (34 m), 90° total field of view
Sensitivity: 310 ft (95 m), 140 ft (43 m), and 70 ft (21 m) for high, medium, and low sensitivities, respectively. Maximum distance for a 1 square foot (0.093 m2) n-heptane fire to be reliably detected. For settings see Switch Selectable Options.
* Maximum specified FOV is the angle at which FL5000 can detect the flame at 50% of the maximum specified range. To comply with the directional dependence requirements for EN 54-10:2002, an angle of ± 30° from 0°(0° = Orientation of detector in same axes as flame source) should not be exceeded, based on lab testing at a distance of approximately 5.9 ft (1.8 m).

NOTE: Response Times and Field of View data were obtained from tests with a 1 square foot heptane fire. These are typical values and different results may occur depending on the variation of each fire.

Mechanical Specifications

Enclosure Material: 316 Stainless Steel
Color: Red
Finish: Polyester TGIC Powder Coating
Vibration: Tested to the vibration requirements of FM 3260, EN 54-10 and DNV-CG-0339 (Class A)

Dimensions

Height: 4.17" (106 mm)
Diameter:

5.44” (138 mm) Base
3.47" (88 mm) Optical Housing

Weight: 7.6 lbs (3.447 kg)
Weight (w/ mount bracket):
9.125lbs (4.139 kg)

Environmental Specifications

Operating temperature range:

-40°F to 176°F (-40°C to 80°C) - FM3260 & ULC-ORD-C386

-67°F to 176°F (-55°C to 80°C) - EN54-10 & DNV-CG-0339

Storage temperature range:

-40°F to 176°F (-40°C to 80°C) - FM3260 & ULC-ORD-C386

-67°F to 176°F (-55°C to 80°C) - EN54-10 & DNV-CG-0339

Humidity range: 0% to 95% RH, non-condensing
Maximum use altitude: 2000 m above sea level

Electrical Specifications*

* See Certifications for Certifications
Nominal supply voltage: 24 VDC (5.7 W with Heater 'OFF', 8.9 W with Heater 'ON')
Range: 20 to 32 VDC
Maximum power consumption:
6.2 W (heater ‘OFF’)
9.7 W (heater ‘ON’)
Spectral range: 2 – 5 microns (IR)
Maximum output signal load: 600 Ω @ 24 VDC

* HART (1.25 mA) is the default.

NOTE: Refer to the FL5000 Modbus or HART manual for Current Range selection.

  HART (1.25 mA) * HART (3.5 mA) HART Disabled/OFF
Output signal range: 1.25 – 20 mA 3.5 – 20 mA 0 to 20 mA
FAULT signal: 1.25 mA 3.5 mA 0 to 0.2 mA
COPM fault signal: 2.0 ± 0.2 mA 3.5 mA 2.0 ± 0.2 mA
Ready signal:

4.05 ± 0.2 mA

4.05 ± 0.2 mA

4.3 ± 0.2 mA
INSTANT ALARM signal:

16.0 ± 0.2 mA

16.0 ± 0.2 mA

16.0 ± 0.2 mA
SUSTAINED ALARM signal:

20.0 ± 0.2 mA

20.0 ± 0.2 mA

20.0 ± 0.2 mA
Bluetooth load: 3.0 mA 3.0 mA 3.0 mA
* Modbus Communication field wiring terminals are intended for device setup and programming purposes only.
Relay Contact Ratings: 8 A @ 24 VDC, Resistive MAX
RS-485 Output: Modbus* - 128 units in series MAX (247 units with repeaters)
Baud Rate:

2400, 4800, 9600, 19200, and 38400 Baud
(See Terminal Connections 3-4 for Alarm Output Connections)

Status Indicator: Two LEDs indicate status, fault conditions

Product Certification

See Certifications for FM approval (electrical safety, hazardous locations [division/zone], flame performance [FM 3260/ULC-ORD-C386/EN 54-10], functional safety [SIL]), CSA certification (electrical safety, hazardous locations [division]) and DNV certification (maritime).