Specifications
System Specifications
Typical Response Time: | 10 seconds, see Certifications for FM Approval response times |
Field of View*: | ±30° @ 210 ft (64 m), ±45° @ 110 ft (34 m), 90° total field of view |
Sensitivity: | 310 ft (95 m), 140 ft (43 m), and 70 ft (21 m) for high, medium, and low sensitivities, respectively. Maximum distance for a 1 square foot (0.093 m2) n-heptane fire to be reliably detected. For settings see Switch Selectable Options. |
* Maximum specified FOV is the angle at which FL5000 can detect the flame at 50% of the maximum specified range. To comply with the directional dependence requirements for EN 54-10:2002, an angle of ± 30° from 0°(0° = Orientation of detector in same axes as flame source) should not be exceeded, based on lab testing at a distance of approximately 5.9 ft (1.8 m). |
NOTE: Response Times and Field of View data were obtained from tests with a 1 square foot heptane fire. These are typical values and different results may occur depending on the variation of each fire.
Mechanical Specifications
Enclosure Material: | 316 Stainless Steel |
Color: | Red |
Finish: | Polyester TGIC Powder Coating |
Vibration: | Tested to the vibration requirements of FM 3260, EN 54-10 and DNV-CG-0339 (Class A) |
Dimensions
Height: | 4.17" (106 mm) |
Diameter: |
5.44” (138 mm) Base |
Weight: | 7.6 lbs (3.447 kg) |
Weight (w/ mount bracket): |
9.125lbs (4.139 kg) |
Environmental Specifications
Operating temperature range: |
-40°F to 176°F (-40°C to 80°C) - FM3260 & ULC-ORD-C386 -67°F to 176°F (-55°C to 80°C) - EN54-10 & DNV-CG-0339 |
Storage temperature range: |
-40°F to 176°F (-40°C to 80°C) - FM3260 & ULC-ORD-C386 -67°F to 176°F (-55°C to 80°C) - EN54-10 & DNV-CG-0339 |
Humidity range: | 0% to 95% RH, non-condensing |
Maximum use altitude: | 2000 m above sea level |
Electrical Specifications*
Nominal supply voltage: | 24 VDC (5.7 W with Heater 'OFF', 8.9 W with Heater 'ON') |
Range: | 20 to 32 VDC |
Maximum power
consumption: |
6.2 W (heater ‘OFF’)
9.7 W (heater ‘ON’) |
Spectral range: | 2 – 5 microns (IR) |
Maximum output signal load: | 600 Ω @ 24 VDC |
HART (1.25 mA) * | HART (3.5 mA) | HART Disabled/OFF | |
---|---|---|---|
Output signal range: | 1.25 – 20 mA | 3.5 – 20 mA | 0 to 20 mA |
FAULT signal: | 1.25 mA | 3.5 mA | 0 to 0.2 mA |
COPM fault signal: | 2.0 ± 0.2 mA | 3.5 mA | 2.0 ± 0.2 mA |
Ready signal: |
4.05 ± 0.2 mA |
4.05 ± 0.2 mA |
4.3 ± 0.2 mA |
INSTANT ALARM signal: |
16.0 ± 0.2 mA |
16.0 ± 0.2 mA |
16.0 ± 0.2 mA |
SUSTAINED ALARM signal: |
20.0 ± 0.2 mA |
20.0 ± 0.2 mA |
20.0 ± 0.2 mA |
Bluetooth load: | 3.0 mA | 3.0 mA | 3.0 mA |
Relay Contact Ratings: | 8 A @ 24 VDC, Resistive MAX |
RS-485 Output: | Modbus* - 128 units in series MAX (247 units with repeaters) |
Baud Rate: |
2400, 4800, 9600, 19200, and 38400 Baud
|
Status Indicator: | Two LEDs indicate status, fault conditions |
Product Certification
See Certifications for FM approval (electrical safety, hazardous locations [division/zone], flame performance [FM 3260/ULC-ORD-C386/EN 54-10], functional safety [SIL]), CSA certification (electrical safety, hazardous locations [division]) and DNV certification (maritime).